Spray Polyurethane Foam (SPF) Insulation Nuisance Odor Investigations

IAQSWith the rapid increase in the “Green” movement and the push for more energy efficient homes spray polyurethane foam SPF insulation is growing substantially.  As with most new building products the industry has had its own set of unique challenges that include the recognized need for training and certification for installers. Along with the recognized need for training are the results of inadequate applicator training, nuisance odors and occupant sensitivity.  These occupant related complaints have led to a rise in SPF insulation investigations by many who have little understanding of SPF insulation and how it can alter the indoor environment even when correctly installed.


When it comes to the investigation of nuisance odors associated with the application of spray polyurethane foam SPF insulation, I’ve found that most of the investigations typically involve little more than varied attempts at trying to chemically associate the odor with the off-gassing of the SPF.


I’ve been assessing spray polyurethane foam insulation SPF for several years on too many properties to list. I’ve assessed a dozen or so product lines both closed and open cell for manufactures, builders, homeowners, and applicators. The properties ranged from universities, community centers, offices, homes, both new construction and retrofit applications.


In my experience, SPF investigations can be categorized in three distinct categories. The first two seem to be the primary areas of SPFI investigations. The first category is simply miss-applied SPF, the second is presence of pre-existing or recently introduced contaminants and the third would be occupant exposure and sensitization during SPF application.


By using these three assessment categories, I have had great luck in identifying the catalyst of the odor and associated complaint.  It has also helped raise awareness that it’s not always the SPF.


The first category – Category 1 Miss-applied SPF Insulation category


These nuisance odors are directly associated with incorrectly applied SPF insulation and can be addressed by either correcting the areas of miss-applied foam or by removing and re-insulating the areas. Miss-Applied includes improper ventilation during the application, incomplete application, off ratio application, and also includes the SPF in direct contact with recessed can lights in the attic, keyless light fixtures bulbs, dryer vents, and/or chimney flues, all of which can heat the SPF and cause a tremendous amount of chemical odors.


Category 1 is relatively cut and dry and requires the onsite inspection of the SPF and the collection of no air samples.  The inspection of the foam and the determination of correct and complete installation is a critical first step.


I‘ve been on SPF insulation investigations where other Indoor Environmental Professionals (IEP’s) who were hired to assess the SPF insulation never looked at the SPF insulation.  Most have no knowledge of how to assess the correct or complete installation of the SPF insulation.  Most IEP’s show up with all manner of air sampling equipment and begin and end their investigation with the collection of air samples intending to identify the chemical signature of miss-applied SPF insulation.  But that’s just not going to happen.


For all who want to conduct SPF insulation inspections, start with understanding what correct and complete installation is according to the manufacturer who produced the foam you are inspecting.


Below is an example of a home with retro-fit SPF insulation installed in the attic.  The homeowners hired an IEP to help establish and/or confirm that the SPF insulation was making them sick.  The home was traditionally ventilated with a large rear lanai.   As with typical SPF insulation landscape fabric was used to separate the lanai attic from the sealed SPF insulation attic.  However, the large Lanai attic space was not properly ventilated as shown in Diagram 1.

IAQS  #IAQS

The lanai had soffit vents and no off ridge vents hence the incomplete attic ventilation.  The outdoor air pressure (wind) was moving the hot humid Florida air into the attic and into the sealed SPF insulation attic through the landscape fabric and SPF insulation as shown in Diagram 3.  The moisture was supporting microbial growth that was the actual odor identified within the home.  The correction was to first relieve the lanai attic pressure by installing an off ridge vent as shown in Diagram 2 and then by removing and replacing the mold damaged SPF insulation.

IAQS

Unfortunately, thousands of dollars were spent on the hunt for the infamous miss-applied chemical signature of the off-gassing SPF insulation.  Of course to no avail.  This is just one example of the easily overlooked yet painfully obvious issues with incomplete or incorrect SPF insulation.

The second category – Category 2 pre-existing or recently introduced contributors


This category cannot be stress enough to the professionals that are investigating SPFI.  This category runs the gamut and can include some rather odd contributors to occupant discomfort and nuisance odors that become much more concentrated when the SPFI is installed.   These include the HVAC system, air exchange rate, storage of materials in the now sealed space, insect and or rodent activity, routine pest control applications, the previous insulation condition and material, proper ducting of kitchen and bath fans.  The possibilities are endless and all must be considered.  Remember that what has accumulated in the attic is now semi-conditioned air that is shared with the attic and living space of the home.


For example if the home is a 60 year old ranch that had open cell SPFI installed at the roof sheathing and the attic was not cleaned to help save a few bucks, the bath fans are ducted to the attic space, and the home once had a rodent issue that was treated with poisons.  Well to say the least you have a huge list of contributors to occupant discomfort and nuisance odors.  Most of the SPF insulation investigations I am called in to review all of these issues were overlooked simply because of the recent application of SPFI.


It’s not necessarily the SPF insulation that is producing the odor or contaminate that is causing occupant discomfort but the SPF insulation is what eliminated the natural ventilation of the attic which prevented the odors and contaminants from entering the home.  The SPF insulation has now trapped the odors and contaminants within the semi-conditioned space.


In this case, the home also had no outdoor air and the home was accumulating VOC’s from daily use products.


The home was blower-door tested and didn’t even come close to the minimum ASHRAE air exchange rate. That attic air is now a part of the occupied space as semi-conditioned space and has 60 years of accumulated who knows what.  Easily it could include the accumulation of dust, debris, fiberglass, rodent and insect activity, prior application of pesticides, maybe even vermiculite.


This is a huge aspect of an SPF insulation investigation that I find all too often overlooked. As a professional investigating SPF insulation you have to ask questions beyond the obvious who was the demon SPF insulation manufacturer.


You have to ask relevant questions such as;

  • “What is the condition of the new semi-conditioned space?”
  • “What have the occupants been sealed in with?”
  • “How is the air exchange rate being met?”
  • “How is the semi-conditioned space actually being semi-conditioned?”


Sometimes it’s best to keep it simple, particles, pathway, and pressure.  Remember to keep an opened mind; it’s not always the SPF insulation.


On a retrofit SPF insulation investigation where there was an odor described as rotten eggs or sulfur the home owner hired an IEP to help establish that the SPF insulation was making them sick.  The IEP’s hired to find the odor focused on TO-15 sample collection throughout the home.  They were confident they identified the miss-applied SPF insulation chemical signature.


Not quite. Just under $5,000 later it was determined that the samples identified a chemical cocktail that could have been the result of just about everything used within the home over the last year since the SPF insulation was applied.  With no outdoor air supply and poor ventilation the VOC’s created within the home stayed in the home.  What the IEP’s didn’t notice was a failed air admittance valve in the attic over the area where the odor was the strongest.  At a cost of twenty bucks for a new air admittance valve the odor was eliminated.


On a new construction SPF insulation investigation, the IEP’s hired to establish that the SPF insulation was making the homeowners sick once again set up the VOC sample collection center and collected four TO-15 8 hour summa canisters and 8 sorbent tubes from a single story 2,200 square foot home.


The homeowners reported that after about a year the home began to make them feel worse when home than when away.  The culprit in their mind was the SPF insulation.  When I asked them how they came to that conclusion they said Google. They then hire an IEP to help them prove to the builder that the SPF insulation was making them sick.


As the IEP was setting up their summa canisters, I began my investigation that started with the condition and settings of the homes ventilation system.  I knew the home had outdoor air supply.  I simply wanted to determine the thermostat and Aprilaire settings and establish the amount of outdoor air being supplied to the home.  As shown in the photo the Aprilaire ventilation controller was set to “Off”.

IAQS

When the 8 hour sampling period was over and the IEP was collecting their equipment I cranked up the AC and opened the Aprilaire ventilator to 30 minutes per cycle. During the sampling period of 8 hours the carbon dioxide levels were measured above 2000 ppm and the tVOC’s were measured at a mere 700 to 800 ppb.  After 1 hour of proper ventilation the carbon dioxide and tVOC levels were reduced by more than 50%. Amazingly the issue proved to be accumulation and not production of VOC’s.  Once again a complete investigation identified an issue with the ventilation that was misdiagnosed as SPF insulation.


On another SPF insulation investigation were the homeowner had spent thousands on sampling with an IEP who felt he had established the connection between the SPF and the occupant symptoms.  Again review by the PhD’s and chemist found no such connection that could be corroborated.  However the interview found that the homeowner was in the second floor master bedroom during the application of the SPF insulation.  The access to the attic was in the master closet, nice.  The applicator didn’t want to use landscape fabric to separate the large covered second story balcony just outside of the master bedroom so the applicator just applied the SPF insulation to the ceiling of the balcony.

IAQS

The photos above show two of the nine recessed can light fixtures that were covered in the foam from completely covered to just shy of completely covered.  The homeowner liked to sit outside in the evening and look out over the lake.  However, he reported that he could no longer spend the evenings on his beloved balcony because he was so sensitive to the SPF insulation. Yes he had become sensitized to the SPF insulation because he was in the home during the application but the trigger or catalyst to the odor was the heating of the SPF insulation just outside his master bedroom and just above his beloved balcony each time he turned on the balcony lights.


Sometimes as IEP’s we are hired to provide a very specific service.  I’ll use mold as an example.  When some IEP’s are hired to provide a mold inspection they often become far too focused on looking for one potential contributor and often overlook the many other and often obvious contributors.  Samples for mold spores are collected and moisture is hunted with a vengeance but not much else is looked at or investigated.   SPF insulation investigations are the same.  Are we hired to help the homeowner identify what in their home may be contributing to their symptoms or are we there to prove their hypothesis that it is or isn’t mold or SPF insulation.


IEP’s often go in with blinders on and lose focus on the true intent of the investigation which in my opinion should be “What is contributing to occupant discomfort and complaint?”   The IEP should approach the home as a system and be open to all potential contributors to occupant complaint.  The chief characteristic that distinguishes the scientific method of investigation from other methods of investigation is that scientists seek to let reality speak for itself, supporting a theory when a theory’s predictions are confirmed and challenging a theory when its predictions prove false.  Scientific investigation is generally intended to be as objective as possible in order to reduce biased interpretations of results. This is often overlooked when the IEP conducts an investigation focused on making the evidence support their hypothesis without objective challenge.


IEP’s must remember that while the SPF insulation may be the issue unless you can say there are no other issues within the home you have not completed your investigation you have just begun.


The third category – Category 3 Sensitization due to exposure


This category includes all occupants who have become sensitized or allergic to the odors given off from SPFI. With sensitization occupants have either re-entered the property shortly after the foam is applied, well before the manufacturer recommended re-occupancy time of 24 to 48 hours while the SPF insulation is still curing and off-gassing, or in the most severe cases of occupant sensitivity the exposure was actually took place during the application of the SPF insulation.


I had one case where the sensitized occupant was also the general contractor that built the home.  During the interview with the owner builder, I asked what he knew as a builder about the SPF insulation.  He admitted to not knowing anything until he began to react to the SPF insulation in his home.  I asked if he had the MSDS to review and he informed me that he did not.  Interesting, I asked if he maintained all of the building material MDS onsite.  He happily sad no that’s up to the subcontractors, interesting.


I then asked him if he was curious as to how the SPF insulation was applied and he of course told me that he was very curious.  He told me that he was in the attic while it was being applied.  Incredible right, you can’t make this up.


I asked if he thought it was odd that the applicator was in full protective equipment with supplied air and he was just watching in street clothes.  I also asked if the contractor told him that he shouldn’t be watching without personal protective equipment.  He told me that the contractor told him that he shouldn’t be up there when it was being applied but it was his house and he was the builder so he was going to do what he wanted.  I asked how long he was up there and he said about 30 minutes and then he began to get a huge headache.  Unbelievable, he was incredibly sensitized to the foam and no amount of miss-applied SPF insulation removal was going to provide him any relief.


Sensitization of the occupants can be a result of many issues such as occupants that don’t want to spend the money for a hotel stay, early re-entry or occupancy, the curious application observer, to the painfully stupid like the builder above.  However occupant sensitization can also be the result of the lack of proper ventilation during the application.  Venting of the off-gassing of the SPF insulation during application is critical and often not conducted at all. In all cases of occupant sensitization that I have been involved with the SPF insulation application was not properly vented to the exterior which created a substantial accumulation of the off-gassing chemicals within the property. These trapped volatile organic chemicals VOC’s are what sensitizes the occupants who have either re-occupied too early or were present during the SPFI application.


Sensitization occurs when the occupants are overexposed to the trapped volatile organic chemicals VOC’s and become sensitized. From that point on, any exposure to even a minute amount of the chemical causes a reaction. The process of sensitization can make a home unlivable for people who become sensitized.


Homes that have improper ventilation during the application process of the SPF insulation are also included in the miss-applied category and almost always have identified areas of miss-applied SPF insulation (SPFI).


This category is unique in that any attempt at reducing the occupant’s exposure to the SPF insulation that they are now sensitized to may not be of any relief.  I have had no luck in providing sensitized occupants relief from the home they are now sensitive to.  I have been involved in everything from the introduction of outdoor air through a pre-filter and dehumidifier to control the temperature, humidity, particles, path, and pressure to full removal of the SPF insulation. Unfortunately that bell can’t be un-rung.


Steps in the Right Direction


SPFA’s The Spray Polyurethane Foam Professional Certification Program (“SPFA PCP”) launched at the SprayFoam 2013 Convention & Expo

IAQS

To become certified under SPFA’s new program, you must pass the exam and meet the criteria for any level of Certification you would like to achieve. It is a progressive program with each level based on the candidate passing the exam for the previous level. In other words, EVERYONE must begin with SPF Assistant criteria. If your ultimate goal is to be a Certified Project Manager, you must meet the requirements for Assistant, then Installer, then Master Installer, then Project Manager to become a Certified SPF Project Manager. http://www.sprayfoam.org/


Connecticut House Bill No. 5908; An act requiring safety and certification standards for the spray foam insulation industry


ASTM WK30960 is intended to establish safe re-entry times for occupants following spray polyurethane foam insulation application.


ASTM WK30960 - New Practice for Spraying, Sampling, and Packaging Spray Polyurethane Foam (SPF) Insulation Samples for Environmental Chamber Emissions Testing


The CAN/ULC S705.1 National Standard requires that the spray polyurethane foam material be installed in accordance with the CAN/ULC S705.2 standard for Thermal insulation – Spray applied rigid polyurethane foam, medium density – Application.


The CAN/ULC S705.2 Application Standard lists a number of requirements for the manufacturer (seller of the two liquid components), the contractor (the corporation who has the contract to perform the installation) and the installer (the worker who actually sprays the components to form spray polyurethane foam on the job site).


The CAN/ULC S705.2 Application Standard sets forth requirements for environmental conditions suitable for spraying, substrate requirements, installation requirements, daily testing of the installed products and documentation requirements.


The Licensed Contractor is required to use applicators that are trained and certified under the SPF Quality Assurance Program used by CUFCA. Each installer is issued a plastic photo-identification card every July 1. The installer is required to carry this card with him during the complete installation period.



John P. Lapotaire, CIEC
Certified Indoor Environmental Consultant
Indoor Air Quality Solutions, IAQS
Microshield Environmental Services, LLC
Certification by American Council for Accredited Certification ACAC CIEC #0711048
Council-certified Environmental Thermography Consultant ACAC CETC #1005013
Accreditation by Council for Engineering and Scientific Specialty Boards (CESB)
Florida State License Mold Assessor MRSA #4

www.FloridaIAQ.com



 

Add a Comment

(Enter the numbers shown in the above image)


Follow jlapotaire on Twitter


Review microshield-es.com on alexa.com
   

[Valid RSS]
Add this Content to Your Site
   


Latest Top (12) News


EPISODE511: Chuck Violand, Ross Riek, Owen Boak and The Restoration Global Watchdog!
This past June RIA held its first International restoration conference and trade show on Australia’s beautiful Sunshine Coast. The event which will be an annual offering in the region was organized and delivered by RIA’s Australasian Council. The local RIA conference planning committee collaborated with the Australian IAQA chapter leadership and featured several education sessions by local leading IAQ experts. Mold seemed to be a hot topic at the conference with several labs exhibiting at the trade show! The event was also attended by IICRC leadership and several other regional dignitaries from related segments of the cleaning, restoration and remediation industries.

Thu, 03 Jan 2019 15:00:00 -0600


EPISODE497 - Radio Joe and the Z-man – Using Building Science & EPA’s Moisture Control Guide to Improve Indoor Air!
Today Radio Joe and the Z-man will be discussing how to solve indoor environmental quality problems by using building science fundamentals and the “EPA Moisture Control Guide”. To get at the root of IEQ problems you must understand buildings and building science. Today we will discuss some great information from people like Joe Lstiburek, Terry Brennan, Bill Rose, Mike McGuinness and Lew Harriman. We start with an overview of building science concepts that will help you solve problems. Our foundation will be the 4 P’s (people, pollutant, pathway, pressurization). From there we will go into how to use the wealth of information in the EPA “Moisture Control Guide” and then go through some case studies. On a future show we will get into how to include the information in your reports

Thu, 11 Oct 2018 11:00:00 -0500


EPISODE509: Nick Hurst – US EPA, Indoor Environments Division – The EPA Indoor airPLUS Program
This week on IAQradio+ we welcome Nick Hurst. Nick is an Environmental Protection Specialist with the US EPA and the Program Manager of EPA’s Indoor airPLUS label for new homes. He has been involved in the construction industry for over 17 years as a self-employed remodeling contractor, project manager, green building consultant, and trainer. Nick earned a Master’s in Technology concentrating in Building Science from Appalachian State University in Boone, NC, and he later served as Education and Outreach Director for the North Carolina Energy Efficiency Alliance at ASU’s Energy Center. Before coming to EPA, Nick also worked as a consultant at ICF in their Federal Energy Efficiency portfolio. Nick is also a BPI Building Analyst and participates with a number of standard setting organizations and technical committees in the building industry.

Fri, 29 Jun 2018 15:30:00 -0500


EPISODE508: HOMEChem Open House – House Observations of Microbial and Environmental Chemistry
This week on IAQradio+ will be broadcasting live from the Open House event for the HOMEChem study at the University of Texas Austin’s, J.J. Pickle Research Campus. The HOMEChem experiment (House Observations of Microbial and Environmental Chemistry) incorporates state-of-the-art measurements performed by over 20 investigators and their teams from the fields of chemistry, microbiology, and engineering. This experiment engages far more institutions and disciplines than ever applied to the study of a home. This research study is sponsored by the Alfred P. Sloan Foundation Chemistry of Indoor Environments Program and it will take place this summer at the University of Texas at Austin’s UTest House. Our guests for this special show are Marina Vance (HOMEChem Co-PIs / organizer) Delphine Farmer (HOMEChem Co-PIs / organizer) Atila Novoselac (HOMEChem host, specialist on the UTest house) Rich Corsi (HOMEChem host, indoor air specialist) Dr. Richard L. Corsi is the Joe J. King Chair in Engineering #2 in the Department of Civil, Architectural and Environmental Engineering (CAEE) at The University of Texas at Austin (UT Austin). He has served on the faculty of CAEE at UT Austin for nearly 25 years, after starting his career in the School of Engineering at the University of Guelph in Ontario, Canada. Dr. Corsi is highly regarded as an educator. He has received numerous teaching awards, and in 2015 was inducted into the Academy of Distinguished Teachers, an honor held for the top 5% of teachers across UT Austin. He also received a Regents’ Outstanding Teaching Award for the entire UT system in 2016. Dr. Corsi’s research focuses on sources, physics and chemistry of indoor air pollution, particularly as related to pollutant interactions with indoor materials and innovative strategies for using such interactions to reduce human exposure to air pollution of both outdoor and indoor origin. He has served as principal investigator on over 70 projects, as major advisor to over 50 undergraduate and 70 graduate students, and as co-author on over 300 journal/conference papers, reports, and book chapters. His work has been featured in National Geographic, The Economist, Business Week, National Wildlife, Prevention, Men’s Health, National Public Radio’s Science Friday, Science Studio, the Academic Minute, the Canadian television series The Nature of Things, and more. Delphine Farmer, PhD Dr. Delphine Farmer is an Associate Professor in the Department of Chemistry at Colorado State

Fri, 22 Jun 2018 15:30:00 -0500


EPISODE508: HOMEChem Open House – House Observations of Microbial and Environmental Chemistry
This week on IAQradio+ will be broadcasting live from the Open House event for the HOMEChem study at the University of Texas Austin’s, J.J. Pickle Research Campus. The HOMEChem experiment (House Observations of Microbial and Environmental Chemistry) incorporates state-of-the-art measurements performed by over 20 investigators and their teams from the fields of chemistry, microbiology, and engineering. This experiment engages far more institutions and disciplines than ever applied to the study of a home. This research study is sponsored by the Alfred P. Sloan Foundation Chemistry of Indoor Environments Program and it will take place this summer at the University of Texas at Austin’s UTest House. Our guests for this special show are Marina Vance (HOMEChem Co-PIs / organizer) Delphine Farmer (HOMEChem Co-PIs / organizer) Atila Novoselac (HOMEChem host, specialist on the UTest house) Rich Corsi (HOMEChem host, indoor air specialist) Dr. Richard L. Corsi is the Joe J. King Chair in Engineering #2 in the Department of Civil, Architectural and Environmental Engineering (CAEE) at The University of Texas at Austin (UT Austin). He has served on the faculty of CAEE at UT Austin for nearly 25 years, after starting his career in the School of Engineering at the University of Guelph in Ontario, Canada. Dr. Corsi is highly regarded as an educator. He has received numerous teaching awards, and in 2015 was inducted into the Academy of Distinguished Teachers, an honor held for the top 5% of teachers across UT Austin. He also received a Regents’ Outstanding Teaching Award for the entire UT system in 2016. Dr. Corsi’s research focuses on sources, physics and chemistry of indoor air pollution, particularly as related to pollutant interactions with indoor materials and innovative strategies for using such interactions to reduce human exposure to air pollution of both outdoor and indoor origin. He has served as principal investigator on over 70 projects, as major advisor to over 50 undergraduate and 70 graduate students, and as co-author on over 300 journal/conference papers, reports, and book chapters. His work has been featured in National Geographic, The Economist, Business Week, National Wildlife, Prevention, Men’s Health, National Public Radio’s Science Friday, Science Studio, the Academic Minute, the Canadian television series The Nature of Things, and more. Delphine Farmer, PhD Dr. Delphine Farmer is an Associate Professor in the Department of Chemistry at Colorado State

Fri, 22 Jun 2018 15:30:00 -0500


EPISODE508: HOMEChem Open House – House Observations of Microbial and Environmental Chemistry
This week on IAQradio+ will be broadcasting live from the Open House event for the HOMEChem study at the University of Texas Austin’s, J.J. Pickle Research Campus. The HOMEChem experiment (House Observations of Microbial and Environmental Chemistry) incorporates state-of-the-art measurements performed by over 20 investigators and their teams from the fields of chemistry, microbiology, and engineering. This experiment engages far more institutions and disciplines than ever applied to the study of a home. This research study is sponsored by the Alfred P. Sloan Foundation Chemistry of Indoor Environments Program and it will take place this summer at the University of Texas at Austin’s UTest House. Our guests for this special show are Marina Vance (HOMEChem Co-PIs / organizer) Delphine Farmer (HOMEChem Co-PIs / organizer) Atila Novoselac (HOMEChem host, specialist on the UTest house) Rich Corsi (HOMEChem host, indoor air specialist) Dr. Richard L. Corsi is the Joe J. King Chair in Engineering #2 in the Department of Civil, Architectural and Environmental Engineering (CAEE) at The University of Texas at Austin (UT Austin). He has served on the faculty of CAEE at UT Austin for nearly 25 years, after starting his career in the School of Engineering at the University of Guelph in Ontario, Canada. Dr. Corsi is highly regarded as an educator. He has received numerous teaching awards, and in 2015 was inducted into the Academy of Distinguished Teachers, an honor held for the top 5% of teachers across UT Austin. He also received a Regents’ Outstanding Teaching Award for the entire UT system in 2016. Dr. Corsi’s research focuses on sources, physics and chemistry of indoor air pollution, particularly as related to pollutant interactions with indoor materials and innovative strategies for using such interactions to reduce human exposure to air pollution of both outdoor and indoor origin. He has served as principal investigator on over 70 projects, as major advisor to over 50 undergraduate and 70 graduate students, and as co-author on over 300 journal/conference papers, reports, and book chapters. His work has been featured in National Geographic, The Economist, Business Week, National Wildlife, Prevention, Men’s Health, National Public Radio’s Science Friday, Science Studio, the Academic Minute, the Canadian television series The Nature of Things, and more. Delphine Farmer, PhD Dr. Delphine Farmer is an Associate Professor in the Department of Chemistry at Colorado State

Fri, 22 Jun 2018 15:30:00 -0500


EPISODE507: Radio Joe & Bob Krell Report LIVE – IAQA Mid Atlantic Conference – Eva King, PhD & Wei Tang, PhD
This week on IAQradio+ and Healthy Indoors Magazine are coordinating on a live show from the IAQA Mid Atlantic Conference in Princeton, New Jersey. Today’s guests include Eva King, PhD and Wei Tang, PhD. Dr. Eva King, CIEC is the Principal Scientist and Founder of AURA EnviroScience. Eva received her Masters degree in Biochemistry from the University of Bielefeld, Germany, and her Doctorate from the University of Oxford, UK. Dr. Wei Tang is the founder, President and Laboratory Director of QLab in Metuchen, New Jersey. Dr. Eva King, CIEC is the Principal Scientist and Founder of AURA EnviroScience. Eva received her Masters degree in Biochemistry from the University of Bielefeld, Germany, and her Doctorate from the University of Oxford, UK. She has been involved in investigations and research into indoor environments and health, allergens, asthma and immunology for over 10 years, and has developed a wide range of new methods for exposure assessment. She has helped clients in different industry sectors, accelerating product development and validation, and assisted in clinical trials and other research studies. Her work has been published in many peer-reviewed scientific publications. Eva is an active member of the indoor air quality, industrial hygiene, and allergy research communities, and served on the Board of Directors of IAQA, and as Convention Committee Chair between 2013 and 2017. Dr. Wei Tang is the founder, President and Laboratory Director of QLab in Metuchen, New Jersey. Dr. Tang graduated from Cornell University with his Master and Ph.D. degrees in Soil Microbiology. He has conducted numerous research projects in Cornell University Soil Microbiology Laboratory in using microorganisms for bioremediation of environmental organic pollutants. His work in recent years has been focused on microbiological sampling and analysis methods for indoor environmental quality assessment. He has taught professional development courses and presented frequently at national conferences on analysis of indoor microorganisms and also on various topics including investigation and remediation of microbial growth in indoor environment. Dr. Tang is the inventor of several advanced microbial sampling devices including AccuScience Triple Gel-Tape, Sweep-Swab and Sponge-Swab. He also developed several advanced analytical methods such as AccuScience High Performance Spore Count and AccuScience Triplicate Analysis. Dr. Tang served on IAQA Board of Directors for three terms. H

Fri, 15 Jun 2018 15:15:00 -0500


EPISODE507: Radio Joe & Bob Krell Report LIVE – IAQA Mid Atlantic Conference – Eva King, PhD & Wei Tang, PhD
This week on IAQradio+ and Healthy Indoors Magazine are coordinating on a live show from the IAQA Mid Atlantic Conference in Princeton, New Jersey. Today’s guests include Eva King, PhD and Wei Tang, PhD. Dr. Eva King, CIEC is the Principal Scientist and Founder of AURA EnviroScience. Eva received her Masters degree in Biochemistry from the University of Bielefeld, Germany, and her Doctorate from the University of Oxford, UK. Dr. Wei Tang is the founder, President and Laboratory Director of QLab in Metuchen, New Jersey. Dr. Eva King, CIEC is the Principal Scientist and Founder of AURA EnviroScience. Eva received her Masters degree in Biochemistry from the University of Bielefeld, Germany, and her Doctorate from the University of Oxford, UK. She has been involved in investigations and research into indoor environments and health, allergens, asthma and immunology for over 10 years, and has developed a wide range of new methods for exposure assessment. She has helped clients in different industry sectors, accelerating product development and validation, and assisted in clinical trials and other research studies. Her work has been published in many peer-reviewed scientific publications. Eva is an active member of the indoor air quality, industrial hygiene, and allergy research communities, and served on the Board of Directors of IAQA, and as Convention Committee Chair between 2013 and 2017. Dr. Wei Tang is the founder, President and Laboratory Director of QLab in Metuchen, New Jersey. Dr. Tang graduated from Cornell University with his Master and Ph.D. degrees in Soil Microbiology. He has conducted numerous research projects in Cornell University Soil Microbiology Laboratory in using microorganisms for bioremediation of environmental organic pollutants. His work in recent years has been focused on microbiological sampling and analysis methods for indoor environmental quality assessment. He has taught professional development courses and presented frequently at national conferences on analysis of indoor microorganisms and also on various topics including investigation and remediation of microbial growth in indoor environment. Dr. Tang is the inventor of several advanced microbial sampling devices including AccuScience Triple Gel-Tape, Sweep-Swab and Sponge-Swab. He also developed several advanced analytical methods such as AccuScience High Performance Spore Count and AccuScience Triplicate Analysis. Dr. Tang served on IAQA Board of Directors for three terms. H

Fri, 15 Jun 2018 15:15:00 -0500


EPISODE505 - Ed Cross – “The Restoration Lawyer” – Restoration Industry Legal Issues & Answers
This week on IAQradio+ we welcome “The Restoration Lawyer” Ed Cross to discuss current legal issues and answers for restoration professionals. Mr. Cross has built a successful law practice that specially caters to the needs of insurance damage repair contractors and remediators. Mr. Cross received a Bachelor’s Degree in Speech Communications with an emphasis on Public Speaking from California State University at Northridge in 1986 (Dean’s Honor Roll), and his Juris Doctor Degree from Western State University in Fullerton California. Ed is also well known for his risk management advice, cleaning and restoration contracts and related forms available for free and/or for purchase on his website edcross.com . These are simple one page forms in plain English that protect payment rights and deter lawsuits. He has recently added contract forms specific to the needs of those doing work in Texas and Florida.

Fri, 25 May 2018 15:15:00 -0500


EPISODE505 - Ed Cross – “The Restoration Lawyer” – Restoration Industry Legal Issues & Answers
This week on IAQradio+ we welcome “The Restoration Lawyer” Ed Cross to discuss current legal issues and answers for restoration professionals. Mr. Cross has built a successful law practice that specially caters to the needs of insurance damage repair contractors and remediators. Mr. Cross received a Bachelor’s Degree in Speech Communications with an emphasis on Public Speaking from California State University at Northridge in 1986 (Dean’s Honor Roll), and his Juris Doctor Degree from Western State University in Fullerton California. Ed is also well known for his risk management advice, cleaning and restoration contracts and related forms available for free and/or for purchase on his website edcross.com . These are simple one page forms in plain English that protect payment rights and deter lawsuits. He has recently added contract forms specific to the needs of those doing work in Texas and Florida.

Fri, 25 May 2018 15:15:00 -0500


EPISODE502: Tedd Benson – Bensonwood & Unity Homes Bridging the Gap! The Search for a Better Way to Build & Bob Krell – Healthy Indoors Magazine An Industry Update
This week on IAQ Radio+ we look forward to a great discussion on better ways to build and an industry update. Tedd Benson of Bensonwood and Unity Homes and Bob Krell of Healthy Indoors Magazine are our guests this week. Tedd Benson the founder of Bensonwood (1973) and Unity Homes (2012), has devoted his life to developing a better way to build. A key figure in the revival of timber framing in America, he was one of the founders of the Timber Framers Guild of North America (1984) and authored four books on the subject. Through the decades, Bensonwood established itself as a creative leader in timber frame design, engineering, craftsmanship, and CAD-CAM technology.

Fri, 27 Apr 2018 14:45:00 -0500


EPISODE502: Tedd Benson – Bensonwood & Unity Homes Bridging the Gap! The Search for a Better Way to Build & Bob Krell – Healthy Indoors Magazine An Industry Update
This week on IAQ Radio+ we look forward to a great discussion on better ways to build and an industry update. Tedd Benson of Bensonwood and Unity Homes and Bob Krell of Healthy Indoors Magazine are our guests this week. Tedd Benson the founder of Bensonwood (1973) and Unity Homes (2012), has devoted his life to developing a better way to build. A key figure in the revival of timber framing in America, he was one of the founders of the Timber Framers Guild of North America (1984) and authored four books on the subject. Through the decades, Bensonwood established itself as a creative leader in timber frame design, engineering, craftsmanship, and CAD-CAM technology.

Fri, 27 Apr 2018 14:45:00 -0500
Follow Microshields IAQ News and Headlines Bloglines RSS Feed

Subscribe with Bloglines

 



IAQ News and Articles

Latest Top (10) News
http://recordings.talkshoe.com/rss1547.xml